Product Description
System
This product is suitable for AC 50Hz, rated voltage 3.6/35kV(system maximum voltage 1.2kV) power line transmission power.
Occasions
fixed laying in metallurgy, electric power, construction and other industries, indoor, cable trench, pipeline, direct buried and other occasions without mechanical external force.
Product features
The production of raw materials from a wide range of low prices, easy to process manufacturing. The product uses crosslinked polyethylene insulation, compared with PVC insulated cable, good insulation performance, conductor operating temperature is higher, up to 90 degrees.
Standard
compliance GB/T 12706.1-2020 Rated voltage 1kV (Um=1.2kV) to 35kV (Um=40.5kV) Extruded insulated power cables and accessories – Part 1: Rated voltage 1kV (Um=1.2kV) and 3kV (Um=3.6kV) cable additional standard Usage characteristics
Rated voltage
Power frequency AC rated voltage is 3.6/35kV, the use of AC system maximum voltage should not exceed 40.5kV.
Operating temperature
The maximum allowable operating temperature of the conductor for a long time is 90 ° C. In the case of short circuit, the maximum temperature of the cable conductor shall not exceed 250 ° C and the duration shall not exceed 5s.
Ambient temperature
The minimum operating temperature is -40 ° C. Laying temperature The laying temperature of the cable should not be lower than 0 ° C.
Bending radius
The bending radius of a single-core cable should be no less than 20 times the outer diameter of the cable, and the bending radius of a multi-core cable should be no less than 15 times the outer diameter of the cable.
Product identification core
1.Color identification When multi-core cables are marked with different colors, they meet the following requirements:
2-core cables: red, blue;
3-core cable: yellow, green, red;
4 core cable: yellow, green, red, blue; 5-core cable: yellow, green, red, blue, black (or determined by the supply and demand parties). The colors red, yellow and green are used for the main line core. blue
specification | conductor structure | Outer diameter of conductor(mm) | Conductor shield thickness(mm) | insulation thickness (mm) |
Non-metal shielding specifications(mm) | Metal shield specification(mm) | Tape specification(mm) | sheath thickness (mm) |
Reference outside diameter(mm) | Reference weight(kg/km) | 20ºC maximum DC resistance(Ω/km) | testing voltage(kV/min) | Maximum sensitivity of local discharge test(pC) | Maximum allowable tractive force of conductor(N) |
1×50 | 10/2.58 | 8.4 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.1 | 35.2 | 1389 | 0.387 | 73.5/5 | 10 | 3500 |
1×70 | 19/2.18 | 10 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.1 | 36.8 | 1628.6 | 0.268 | 73.5/5 | 10 | 4900 |
1×95 | 19/2.58 | 11.6 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.2 | 38.6 | 1939.3 | 0.193 | 73.5/5 | 10 | 6650 |
1×120 | 24/2.58 | 13 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.2 | 40 | 2217.8 | 0.153 | 73.5/5 | 10 | 8400 |
1×150 | 30/2.58 | 14.6 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.3 | 41.8 | 2561.1 | 0.124 | 73.5/5 | 10 | 10500 |
1×185 | 37/2.58 | 16.2 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.3 | 43.4 | 2935.9 | 0.0991 | 73.5/5 | 10 | 12950 |
1×240 | 48/2.58 | 18.5 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.4 | 45.9 | 3529.2 | 0.0754 | 73.5/5 | 10 | 16800 |
1×300 | 60/2.58 | 20.6 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.5 | 48.2 | 4158.8 | 0.0601 | 73.5/5 | 10 | 21000 |
1×400 | 61/2.94 | 23.8 | 0.8 | 9.3 | 0.7 | 40×0.12 | 60×0.20 | 2.6 | 51.6 | 5133.8 | 0.047 | 73.5/5 | 10 | 28000 |
3×50 | 10/2.58 | 8.4 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 3.3 | 72.5 | 4908 | 0.387 | 73.5/5 | 10 | 10500 |
3×70 | 19/2.18 | 10 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 3.4 | 76.1 | 5731.5 | 0.268 | 73.5/5 | 10 | 14700 |
3×95 | 19/2.58 | 11.6 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 3.5 | 79.8 | 6741.3 | 0.193 | 73.5/5 | 10 | 19950 |
3×120 | 24/2.58 | 13 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 3.6 | 83 | 7681.7 | 0.153 | 73.5/5 | 10 | 25200 |
3×150 | 30/2.58 | 14.6 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 3.7 | 86.6 | 8796 | 0.124 | 73.5/5 | 10 | 31500 |
3×185 | 37/2.58 | 16.2 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 3.8 | 90.3 | 10048.7 | 0.0991 | 73.5/5 | 10 | 38850 |
3×240 | 48/2.58 | 18.5 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 4 | 95.6 | 11997.9 | 0.0754 | 73.5/5 | 10 | 50400 |
3×300 | 60/2.58 | 20.6 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 4.1 | 100.3 | 14022 | 0.0601 | 73.5/5 | 10 | 63000 |
3×400 | 61/2.94 | 23.8 | 0.8 | 9.3 | 0.7 | 40×0.10 | 60×0.20 | 4.4 | 107.8 | 17238.1 | 0.047 | 73.5/5 | 10 | 84000 |